EX) Speed search during Instant Power Failure restart
When the input power is cut off due to instant power failure, the inverter trips (LV).
When the power is restored, the inverter supplies the motor with the frequency stored before
the low voltage trip and the voltage is increased due to speed search PI control.
t1: If current is increasing over the preset level in H23, the voltage increasing will stop and the
frequency is decreased.
t2: If the opposite of t1 occurs, the voltage increasing starts again and the output frequency
stops to decrease.
When the frequency and voltage will reach their nominal level, the inverter will follow the
acceleration ramp until the stored frequency before low voltage (LV) trip is reached.
Speed search operation is suitable for loads with high inertia.
Sinus M keeps normal operation when instant power failure occurs and power is restored in 15msec.
Input
voltage
Frequency
Voltage
Current
H23
t1 t2
Multi-function
output or
Relay