7-16
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
durin
g run
H73
[Monitoring
item select]
0 ~ 2
One of the following can be monitored via
vOL - [User display select].
0
O
0
Output voltage [V]
1
Output power [kW]
2
Torque [kgf
⋅
m]
H74
[Gain for
Motor rpm
display]
1 ~ 1000
[%]
This parameter is used to change the
motor rotating speed (r/min) to mechanical
speed (m/mi) and display it.
100
O
H75
[DB resistor
operating
rate limit
select]
0 ~ 1
0
Unlimited
1
O
1
Use DB resistor for the H76 set
time.
H76
[DB resistor
operating
rate]
0 ~ 30[%]
Set the percent of DB resistor operating
rate to be activated during one sequence
of operation.
10
O
H77
1)
[Cooling fan
control]
0 ~ 1
0
Always ON
0
O
1
Keeps ON when its temp is higher
than inverter protection limit temp.
Activated only during operation
when its temp is below that of
inverter protection limit.
H78
[Operating
method
select when
cooling fan
malfunctions
]
0 ~ 1
0
Continuous operation when cooling
fan malfunctions.
0
O
1
Operation stopped when cooling fan
malfunctions.
H79
[S/W
version]
0 ~ 10.0
This parameter displays the inverter
software version.
1.0
X
H81
[2
nd
motor
Accel time]
0 ~ 6000
[sec]
This parameter actives when the selected
terminal is ON after I17-I24 is set to 12 {2
nd
motor select}.
5.0
O
H82
[2
nd
motor
Decel time]
10.0
O
H83
[2
nd
motor
base
frequency]
30 ~ 400
[Hz]
50.00 X
H84
[2
nd
motor
V/F pattern]
0 ~ 2
0
X
H85
[2
nd
motor
forward
torque boost]
0 ~ 15 [%]
5
X
1)
: Exception: Since Sinus M-0001 2S/T - Sinus M 0001 4T is Natural convection type, this code is
hidden.
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...