Factory default by motor ratings
Input
voltage
Motor rating
[kW]
Current
rating [A]
No-load
current [A]
Rated slip
freq
[Hz]
Stator
resistance [
Ω
]
Leakage
inductance
[mH]
200
0.2
1.1
0.6
2.33
14.0
122.00
0.4
1.8
1.2
3.00
6.70
61.00
0.75
3.5
2.1
2.33
2.46
28.14
1.5
6.5
3.0
2.33
1.13
14.75
2.2
8.8
4.4
2.00
0.869
11.31
3.7
12.9
4.9
2.33
0.500
5.41
5.5
19.7
6.6
2.33
0.314
3.60
7.5
26.3
11.0
2.33
0.196
2.89
11.0
37.0
12.5
1.33
0.120
2.47
15.0
50.0
17.5
1.67
0.084
1.12
18.5
62.0
19.4
1.33
0.068
0.82
22.0
76.0
25.3
1.33
0.056
0.95
400
0.2
0.7
0.4
2.33
28.00
300.00
0.4
1.1
0.7
3.0
14.0
177.86
0.75
2.0
1.3
2.33
7.38
88.44
1.5
3.7
2.1
2.33
3.39
44.31
2.2
5.1
2.6
2.00
2.607
34.21
3.7
6.5
3.3
2.33
1.500
16.23
5.5
11.3
3.9
2.33
0.940
10.74
7.5
15.2
5.7
2.33
0.520
8.80
11.0
22.6
7.5
1.33
0.360
7.67
15.0
25.2
10.1
1.67
0.250
3.38
18.5
33.0
11.6
1.33
0.168
2.46
22.0
41.0
13.6
1.33
0.168
2.84
10.10 Energy-saving operation
Group
Display
Parameter Name
Setting
Range
Default Unit
Function
group 1
F40
[Energy-saving
operation]
-
0 ~ 30
0
%
Set the amount of output voltage to be reduced in F40.
Set as the percent of Max output voltage.
For fan or pump applications, energy consumption can be dramatically reduced by
decreasing the output voltage when light or no load is connected.
Current
Output voltage
F40
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...