7-17
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
H86
[2
nd
motor
reverse
torque boost]
0 ~ 15 [%]
This parameter actives when the
selected terminal is ON after I17-I24 is
set to 12 {2
nd
motor select}.
5
X
H87
[2
nd
motor
stall
prevention
level]
30~150 [%]
150
X
H88
[2
nd
motor
Electronic
thermal level
for 1 min]
50~200 [%]
150
O
H89
[2
nd
motor
Electronic
thermal level
for
continuous]
100
O
H90
[2
nd
motor
rated
current]
0.1~50 [A]
26.3
X
H91
1)
[Parameter
read]
0 ~ 1
Copy the parameters from inverter and
save them into remote keypad.
0
X
H92
1)
[Parameter
write]
0 ~ 1
Copy the parameters from remote
keypad and save them into inverter.
0
X
H93
[Parameter
initialize]
0 ~ 5
This parameter is used to initialize
parameters back to the factory default
value.
0
X
0
-
1
All parameter groups are initialized
to factory default value.
2
Only Drive group is initialized.
3
Only Function group 1 is initialized.
4
Only Function group 2 is initialized.
5
Only I/O group is initialized.
H94
[Password
register]
0 ~ FFFF
Password for H95-[Parameter lock]. Set
as Hex value.
0
O
H95
[Parameter
lock]
0 ~ FFFF
This parameter is able to lock or unlock
parameters by typing password
registered in H94.
0
O
UL (Unlock) Parameter change enable
L (Lock)
Parameter change disable
1)
: H91,H92 parameters are displayed when the Remote option is installed.
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...