13-6
2) Request for Write:
ENQ
Drive No CMD Address
Number of
address to
read
Data
SUM
EOT
05h
“01”~
“1F”
“W”
“XXXX”
“1” ~ “8” = n
“XXXX…”
“XX”
04h
1 byte
2 bytes
1 byte 4 bytes
1 byte
n * 4 bytes
2 byte
1 byte
Total bytes = 12 + n * 4 = Max 44
2.1) Acknowledge response:
ACK
Drive No
CMD
Data
SUM
EOT
06h
“01” ~ “1F”
“W”
“XXXX…”
“XX”
04h
1:byte
2:bytes
1:byte
n * 4 bytes
2 bytes
1 byte
Total bytes = 7 + n * 4 = Max 39
Note) When Request for Write and Acknowledge Response is exchanged between PC and Inverter
for the first time, previous data is returned. From the second time of transmission, the current data
will be returned.
2.2) Negative response:
NAK
Drive No
CMD
Error code
SUM
EOT
15h
“01” ~ “1F”
“W”
“**”
“XX”
04h
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Total bytes = 9
3) Request for Monitor Register
This is useful when constant parameter monitoring and data updates are required.
Request for Register of ‘n’ numbers of Address (not consecutive)
ENQ
Drive No
CMD
Number of
address to read
Address
SUM
EOT
05h
“01” ~ “1F”
“X”
“1” ~ “8”=n
“XXXX…”
“XX”
04h
1 byte
2 bytes
1 byte
1 byte
n * 4 byte
2 byte 1 byte
Total bytes = 8 + n * 4 = Max 40
3.1) Acknowledge Response:
ACK
Drive No
CMD
SUM
EOT
06h
“01” ~ “1F”
“X”
“XX”
04h
1 byte
2 bytes
1 byte
2 bytes
1 byte
Total bytes = 7
3.2) Negative Acknowledge Response:
NAK
Drive No
CMD
Error code
SUM
EOT
15h
“01” ~ “1F”
“X”
“**”
“XX”
04h
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Total bytes = 9
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...