11-12
12: During operation
Activated when run command is ON and inverter output voltage is different from
0.
13: During stop
Activated during stop without output voltage/frequency.
14: During constant speed
Activated during constant speed operation.
15: During speed searching
Refer to page 10-13.
16: Wait time for run signal input
This function becomes active during normal operation and that the inverter waits
for active run command from external sequence.
17: Fault output
The parameter set in I56 is activated.
For example, if setting I55, I56 to 17 and 2, respectively, Multi-function output
relay will become active when trip different from “Low voltage trip” occurred.
18: Cooling fan trip alarm
Used to give an alarm signal when H78 is set to 0 (constant operation at cooling
fan trip). Refer to page 10-21
.
Freq.
MO
Run
command
Freq.
MO
Run
command
Freq.
MO
Run
command