3-6
3.3 Control terminal block
T/M
Terminal Description
Wire size[mm
2
]
Screw
size
Torque
[Nm]
Specification
Single
wire Stranded
P1~P8 Multi-function input T/M 1-8 1.0
1.5
M2.6
0.4
CM
Common Terminal
1.0
1.5
M2.6
0.4
VR
Power supply for external
potentiometer
1.0
1.5
M2.6
0.4
Output voltage: 12V
Max output current:
10mA
Potentiometer:1 ~ 5k
Ω
V1
Input terminal for Voltage
operation
1.0
1.5
M2.6
0.4
Max input voltage:
–12V ~ +12V input
I
Input terminal for Current
operation
1.0
1.5
M2.6
0.4
0 ~ 20mA input
Internal resistor: 250
Ω
AM
Multi-function analog
output terminal
1.0
1.5
M2.6
0.4
Max output voltage:
11[V]
Max output current:
100mA
MO
Multi-function terminal for
open collector
1.0
1.5
M2.6
0.4
Below 26V DC,100mA
MG
MO Common
1.0
1.5
M2.6
0.4
24
24V External Power
Supply
1.0
1.5
M2.6
0.4
Max output current:
100mA
3A
Multi-function relay output
A contact NO
1.0
1.5
M2.6
0.4
Below 250V AC, 1A
Below 30V DC, 1A
3B
Multi-function relay output
B contact NC
1.0
1.5
M2.6
0.4
3C
Common for Multi-function
relays
1.0
1.5
M2.6
0.4
Note 1) Tie the control wires more than 15cm away from the control terminals. Otherwise, it interferes
with front cover reinstallation.
Note 2) Use Copper wires rated 600V, 75°C and higher.
Note 3) Use the recommended tightening torque when securing terminal screws.
Note 4) When you use external power supply (24V) for multi-function input terminal (P1~P8),
terminals will be active above 12V level. Take caution not to drop the voltage below 12V.
3A
3B
3C
P5
CM
P6
P7
P8
VR
V1
I
AM
MO
MG
24
P1
P2
CM
P3
P4
S-
S+
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...