3-4
Section
Wiring
38
Name
Connection type
External interrupt input signal
N.O.
Emergency stop input signal
N.C.
Origin proximity input signal
N.C. or N.O.
CW limit input signal
N.C. or N.O.
CCW limit input signal
N.C. or N.O.
24-VDC
power
supply
External
interrupt
input signal
Emergency
stop input
signal
Origin
proximity
input signal
CW limit
input signal
CCW limit
input signal
680
Ω
4.7 k
Ω
(1/2W)
680
Ω
680
Ω
680
Ω
680
Ω
4.7 k
Ω
(1/2W)
4.7 k
Ω
(1/2W)
4.7 k
Ω
(1/2W)
4.7 k
Ω
(1/2W)
Switch (N.O. contact)
Switch (N.C. contact)
Switch
(N.O./N.C. contact)
Switch
(N.O./N.C. contact)
Switch
(N.O./N.C. contact)
Position Control Unit
3-4-3 Connecting Origin and Positioning Completed Input Signals
The examples below show input connections when open collector sensor output
and the encoder’s Z-phase line driver output are used.
Use a sensor with no chattering, such as a photoelectric sensor, for the origin
input signal.
Caution
Connect a switch with a switching capacity of at least 5 mA to the 24--V origin
input signal terminal.
Caution
Do not connect the 5--VDC origin input signal input to any output circuit except
the line driver.