![Omron CS1W-NC113 - REV 02-2008 Manual Download Page 297](http://html1.mh-extra.com/html/omron/cs1w-nc113-rev-02-2008/cs1w-nc113-rev-02-2008_manual_742370297.webp)
11-4
Section
Reading Error Codes
287
LED
Remedy
Cause
Error
R
U
N
Remedy
Cause
Error
U
Z
Y
X
D
A
T
A
S
E
N
S
E
R
H
E
R
C
f
f
F
l
F
F
F
F
F
Operating data
area designation
error
The designation for
operating data area (m) is
incorrect.
•
Area designation: Set to a
setting other than 00, 0D,
or 0E.
•
Bank designation: Set to a
setting not in the range 00
to 0C, when 0E is set for
the area designation.
In this condition, only the
data save operations can
be performed. The PCU’s
axis parameters and data
are all returned to their
default values. After
correcting the common
parameters (refer to
Section 4
), either reset the
power supply or restart the
PCU.
Response timeout
The axis parameters set in
the PC could not be read to
the PCU.
Increase the cycle monitor
time set with
CX-Programmer and either
reset the power supply or
restart the PCU. If this error
occurs again despite
increasing the cycle
monitor time, it is possible
that there is a fault in the
PCU or somewhere in the
PC. Contact your OMRON
representative.
f
f
F
F
F
F
F
F
F
Operating data
area address
specification error
The beginning word
designation for the
operating data area (m+1)
is outside the settable
range.
In this condition, only the
data save operations can
be performed. The PCU’s
axis parameters and data
are all returned to their
default values. After
correcting the common
parameters (refer to
Section 4
), either reset the
power supply or restart the
PCU.
f
F
F
F
F
--
--
--
--
Normal operation
---
---
f
f
F
F
F
--
--
--
--
Error occurred
An error other than a data
error occurred during
external sensor input.
Check the error code and
correct the error.
f
f
F
f
F
--
--
--
--
External sensor
input
An emergency stop input or
CCW/CW limit input signal
was received.
Check the error code,
verify that it is safe to
proceed, and correct the
error.
f
f
F
F
f
--
--
--
--
Data error
A data inconsistency such
as an out-of-range
parameter occurred.
Check the error code and
correct the error.
f
f
F
f
f
--
--
--
--
External sensor
input data error
An external sensor input
and data error occurred
simultaneously.
The last error that was
detected will be output for
the error code.
11-4 Reading Error Codes
When an error has occurred, an error flag will be turned ON in the operating
memory area and the error code will be input in the operating data area. Check
this code before proceeding with error processing.
The following tables show the allocation of bits for error flags and words for error
codes.