5-5
Section
Reading Data with IORD
120
Operand
Description
C
Specifies the address in the PCU address to be read in hexadecimal.
CPU address (Hex)
W
Specifies the destination unit number from which data will be read
and the total number of words that will be read. The settable ranges
are as follows:
W+1: 0001 to 0080 Hex (128 words)
W:
NC113/133
0000 to 005F Hex (unit numbers: 0 to 95)
NC213/233
0000 to 005F Hex (unit numbers: 0 to 95)
NC413/433
0000 to 005E Hex (unit numbers: 0 to 94)
Example: Reading 9 words of data from unit number 3
#00090003 (total number of words transferred: 0009 (9 words), unit
number: 0003 (3)
Total number of words transferred (Hex)
W+1
W
Destination unit number (Hex)
D
Specifies the first word of the CPU Unit to store the data that will be
read.
Refer to the CS1 manuals for more details.
First destination word
Area
Range
CIO Area (I/O Area etc.)
0000 to 6143
Work Area
W000 to 511
Holding Bit Area
H000 to 511
Auxiliary Area
A448 to 959
Timer Area
T0000 to 4095
Counter Area
C0000 to 4095
DM Area
D00000 to 32767
EM Area
E00000 to 32767
EM Area with bank designa-
tion
En_00000 to 32767 (n=0 to C)
Indirect DM/EM address,
binary
@D00000 to 32767
@E00000 to 32767
En_00000 to 32767 (n=0 to C)
Indirect DM/EM address,
BCD
*D00000 to 32767
*E00000 to 32767
*En_00000 to 32767 (n=0 to C)
5-5-4 Flags
When data is transferred using IORD, the Error Flag (word n+8, bit 12), the ER
Flag and the Equals Flag can be used to check whether the transfer has been
completed successfully. If the Error Flag (word n+8, bit 12) is ON, an error code
will be output to n+10 in the operating memory area. Check this error code to
determine the cause of the error and correct it.