![Omron CS1W-NC113 - REV 02-2008 Manual Download Page 125](http://html1.mh-extra.com/html/omron/cs1w-nc113-rev-02-2008/cs1w-nc113-rev-02-2008_manual_742370125.webp)
5-4
Section
Writing Data with IOWR
113
5-4
Writing Data with IOWR
5-4-1 Outline
The following diagram outlines the way in which positioning sequences are writ-
ten to the PCU.
to
to
to
PCU (NC413)
Data area
Sequence #0 (0 Hex)
Other data
•
Speeds
•
Positions
•
Acceleration
times
•
Deceleration
times
•
Dwell times
•
Zones
Write
C: Beginning address of data.
S: Beginning word address of
transfer source.
W: Transfer destination unit
number and number of transfer
words.
Data
Sequence #1 (1 Hex)
Sequence #99 (63 Hex)
CPU Unit
Refer to
5-4-2 IOWR: Intelligent I/O Write
or the Programmable Controller’s
operation manual for details on how to set the operands for the IOWR instruc-
tion.
1, 2, 3...
1. Set IOWR.
C: Beginning address of the data area in the PCU where the data is to be
stored.
S:
Beginning word address of the area in the CPU Unit in which the data
has been set.
W: Unit number of the PCU which is the transfer destination, and the total
number of words to be read.
2. Set the data.
Set the data in the area designated by S.
3. Write the data.
Execute IOWR.
Data Writing Procedure