![Omron CS1W-NC113 - REV 02-2008 Manual Download Page 279](http://html1.mh-extra.com/html/omron/cs1w-nc113-rev-02-2008/cs1w-nc113-rev-02-2008_manual_742370279.webp)
10-7
Section
Transferring and Saving Data
269
10-7 Transferring and Saving Data
10-7-1 Copying Data
Overview
•
Reading and writing data is carried out according to the number of transfer
words, the transfer source area, the transfer source word, and the transfer
destination address set in the operating data area.
•
This operation can also be used for reading data from a PCU to which data has
already been transferred, and for backing the data up or copying it to another
PCU.
Operation Example
X-axis operating data from an NC213 PCU which has already transferred the
operating data for two axes is read into the DM Area. The operating data set for
the DM Area is written to an NC113 PCU and saved. By combining these two
operations, the NC213’s X-axis data can be copied to the NC113.
Data reading
CS1W-NC213
Parameters/data
X axis only read
Unit #0
Parameters/data
X and Y axes already
transferred.
PC
Data writing, saving
CS1W-NC113
DM Area
D 03000
onwards
Parameters/data
Write, save
Unit #2
Parameters/data
not transferred.
PC
DM Area
D 03000
onwards
READ DATA
1, 2, 3...
1. Mount the NC213 (Unit #0) to the Programmable Controller’s CPU Rack.
Make sure that the data and parameters for both the X and Y axes needed
for the operation of the NC213 (Unit #0) are all transferred.
2. When the operation start switch is turned ON, the parameters and data for
the X axis of the NC213 are read into D03000 through D03799 at the PC.
3. When work bit W03010 turns ON the read operation is completed.
WRITE DATA and SAVE DATA
1, 2, 3...
1. Mount the NC113 (Unit #2) to the Programmable Controller’s CPU Rack.
Set the parameters and data for the X axis of the NC113 in D03000 through
D03799 of the PC.
2. When the operation start switch is turned ON, the parameters and data in
D03000 through D03799 are written to the NC113 and then saved.
3. When work bit W03014 turns ON, the WRITE DATA and SAVE DATA opera-
tions are completed.
Setting the PCU
Unit number: Unit #0
PCU used:
CS1W-NC213
Unit number: Unit #2
PCU used:
CS1W-NC113
READ DATA
WRITE DATA and SAVE
DATA