10-4
Section
Linear Interpolation
262
Address
Setting
Contents of setting
21F4
03E8
Position #0
1000 pulses (3E8 Hex)
21F5
0000
p
(
)
21F6
07D0
Position #1
2000 pulses (7D0 Hex)
21F7
0000
p
(
)
21F8
0BB8
Position #2
3000 pulses (BB8 Hex)
21F9
0000
p
(
)
21FA
0FA0
Position #3
4000 pulses (FA0 Hex)
21FB
0000
p
(
)
21FC
1388
Position #4
5000 pulses (1388 Hex)
21FD
0000
p
(
)
21FE
0000
Position #5
0 pulses (0 Hex)
21FF
0000
p
(
)
2200
0000
Position #6
0 pulses (0 Hex)
2201
0000
p
(
)
Note
Addresses other than the above should be set to their default settings (0).
The origin search acceleration and deceleration times will be used for accelera-
tion and deceleration and so this data needs to be set completely to the default
settings (0).
Dwell times are not used in these programs, so this data area needs to be set
completely to the default settings (0).
Zones are not used in these programs, so this data area needs to be set com-
pletely to the default settings (0).
Program
W030 is used as a work word.
Operation start switch
Takes the rising edge of
the operation start
switch.
Busy Flag
Sets #0 for the
sequence number.
Sequence
Number Enable
Enables the
sequence number.
Start
No Origin
Flag
Only executed
when starting
the first time.
Executed
when starting
from the
second time
onwards.
W03000
200413
200406
W03001
DIFU
W03000
D00516
200000
W03014
W03015
W03001
W03001
W03000
W03001
W03014
W03015
200001
Acceleration and
Deceleration Times
Dwell Times
Zones