![Omron CS1W-NC113 - REV 02-2008 Manual Download Page 302](http://html1.mh-extra.com/html/omron/cs1w-nc113-rev-02-2008/cs1w-nc113-rev-02-2008_manual_742370302.webp)
11-5
Section
Error Code Lists
292
Item
Operation after
error
Clearing
method
Cause
Code
Name
Origin search
Origin detection
method error
1607
Even though the axis parameters’ origin
search operation is set for other than
single-direction mode, the origin
detection method setting is not 0, 1, or 2.
Transfer the
data again after
checking and
correcting it.
When this error
occurs during
data transfer, all
data (including
Backlash
compensation
Backlash
compensation
error
1700
The axis parameters’ backlash
compensation setting is outside the
settable range (0 to 9,999pulses).
g
(
g
the data with the
error) specified
for transfer will
be lost
Backlash
compensation
speed error
1710
The axis parameters’ backlash
compensation speed setting exceeds the
maximum speed setting.
be lost.
All operating
axes will be
decelerated to a
Software
limits
CW software
limit error
1800
The axis parameters’ CW software limit
setting is outside the settable range
(--1,073,741,823 to 1,073,741,823).
decelerated to a
stop.
CCW software
limit error
1801
The axis parameters’ CCW software limit
setting is outside the settable range
(--1,073,741,823 to 1,073,741,823).
Zones
Zone 0 CW
error
1900
Zone 0’s CW data is outside the settable
range (--1,073,741,823 to
1,073,741,823).
Zone 0 CCW
error
1901
Zone 0’s CCW data is outside the
settable range (--1,073,741,823 to
1,073,741,823).
Zone 1 CW
error
1910
Zone 1’s CW data is outside the settable
range (--1,073,741,823 to
1,073,741,823).
Zone 1 CCW
error
1911
Zone 1’s CCW data is outside the
settable range (--1,073,741,823 to
1,073,741,823).
Zone 2 CW
error
1920
Zone 2’s CW data is outside the settable
range (--1,073,741,823 to
1,073,741,823).
Zone 2 CCW
error
1921
Zone 2’s CCW data is outside the
settable range (--1,073,741,823 to
1,073,741,823).
Position data
Target position
error
2000
to
2099
The position data is outside the settable
range (--1,073,741,823 to
1,073,741,823).
(The last two digits of the code indicate
the position data number where the error
occurred.)
Summary of Contents for CS1W-NC113 - REV 02-2008