11-5
Section
Error Code Lists
302
Group
Operation after
error
Clearing method
Cause
Code
Name
Data transfer
Write transfer:
number of
words error
8310
The number of write words was
set to 0 or exceeded the number
of write data words.
The parameters for the origin
search high speed and the origin
search proximity speed were not
sent together.
Execute the
command again
after changing the
incorrect setting.
The current
START command
will not be
executed, but
other operating
axes will not be
affected.
Write transfer:
source word
error
8311
The write source word or the write
source area was outside the
settable range.
Write transfer:
destination
address error
8312
The write destination address was
outside the settable range.
Read transfer:
number of
words error
8320
The number of read words was
set to 0 or exceeded the number
of read data words.
Read transfer:
source address
error
8321
The read source address was
outside the settable range.
Read transfer:
destination word
error
8322
The read destination word or the
read destination area was outside
the settable range.
Error counter
reset/
Origin
adjustment
output
Error counter
reset/
Origin
adjustment
output error
8400
There was an attempt to output a
error counter reset/origin
adjustment output when the
output couldn’t be used.
Execute the
command again
after checking that
the output can be
used and changing
the ladder program
if necessary.
The axis will be
decelerated to a
stop. Other
operating axes will
not be affected.
Override
Override error
8500
The override setting was outside
the settable range (1 to 999%).
Execute the
command again
after correcting the
data.
Positioning
Positioning
timer timeout
8600
The Servo Drive’s positioning
completed signal did not go ON
within the axis parameters’
specified time.
Execute the
command again
after making
adjustments such
as adjusting the
positioning monitor
time or the servo
system’s gain, or
checking the wiring
for the positioning
completed signal
and correcting if
necessary.
The designated
axis will be
decelerated to a
stop.
Other operating
axes will not be
affected.
Overflow
8601
The movement distance is too
long (greater than 2,147,483,646
pulses, or greater than
2,147,483,520 pulses for linear
interpolation) and so operation is
not possible.
Execute the
command again
after reducing the
distance to move in
one operation (by
changing the
position data).
The designated
axis will be
decelerated to a
stop.
Other operating
axes will not be
affected.