
STARTUP AND INITIALIZATION
4-53
Edition One
XC1000 Service
Menu 6 – Dialing and Serial Channel Parameters
– Configure MTA Terminal Channel –
MTA Terminal Number: 1
Baud Rate: 4 – 9600 baud
Terminal Type: 1 – Wyse 50 or HP 700/43
Number of Data Bits: 1 – 8 Data Bits
Data Carrier Detect? (Y/N): N
Number of Stop Bits: 0 – 1 Stop Bits
Parity (No/Odd/Even): 0 – No Parity
Broadcast to this Channel for Dump/IPL? (Y/N): Y
Menu Access Allowed this Terminal
1 – System Parameters: Y
11 – System Dist. Lists: Y
2 – Attendant Schedules: Y
12 – Disk Management Y
3 – Date/Time: Y
13 – System Maintenance: Y
4 – Port Assignments: Y
14 – System Reports: Y
5 – Outcalling Parameters: Y
15 – Network Assignments: Y
6 – Dialing, Serial Channels: Y
16 – Database Access: Y
7 – Class of Service: Y
17 – External Applications: Y
8 – Add Mailbox: Y
18 – X.25 Interface: Y
9 – Change Mailbox: Y
10 – Delete Mailbox: Y
Figure 4-32. Menu 6.4.1, Configure MTA Terminal Channel.
Access menu 6.3 (refer to section 4.8.3) to establish the configuration for
the CPU channel selected. Enter
4
in the
Channel Number to be Defined:
field, and enter either a
2 – PC-based MTA
or
4 – ACP-based MTA
in the
Channel Type:
field. If channel type
4
is selected for the channel type in
menu 6.3, a prompt appears at the bottom of the screen stating that the
MTA channels must be configured in menu 6.4. All fields can be configured
for ACP-based terminals, but only the
Menu Access Allowed this Termi-
nal
fields can be configured for PC-based terminals.
Configure the MTA channels for ACP-based terminals, as follows:
1. From menu 6, select option
4
for MTA parameters (refer to Figure 4-28),
and menu 6.4 appears. Select one of the following options:
1
– Configure MTA Terminals
2
– Review MTA Terminal
2. Select
1 – Configure MTA Terminals
, and menu 6.4.1 appears (Figure 4-32).
3. In the
MTA Terminal Number:
field, enter the number of the terminal to
be defined. Refer to section 3.9.1 for information about MTA terminal
connections.
4. In the
Baud Rate:
field, enter one of the following:
1
– 1200 baud
2
– 2400 baud
3
– 4800 baud
4
– 9600 baud
If only the baud rate is changed, it is stored. Then, if the baud rate
being changed is for the terminal being used, the terminal must be
logged out and then logged in again for the new baud rate to become
active. If the baud rate being changed is for another terminal, that
terminal only has to log on for the change to become active.
In all
cases, before logging back in, reset the baud rate on the affected
terminal by following the steps found in section 4.2.5.
SECTION 4.8
Summary of Contents for XC1000
Page 1: ...EDITION ONE XC1000 P N 101 1345 000 SERVICE MANUAL ...
Page 8: ...CONTENTS ...
Page 19: ...1 INTRODUCTION ...
Page 30: ...2 SITE PREPARATION ...
Page 60: ...3 PLATFORM INSTALLATION ...
Page 112: ...4 STARTUP AND INITIALIZATION ...
Page 177: ...5 ROUTINE MAINTENANCE ...
Page 195: ...6 TROUBLESHOOTING ...
Page 237: ...7 STATUS LOG ...
Page 297: ...STATUS LOG 7 54 Edition One XC1000 Service ...
Page 302: ...8 REPAIR AND REPLACEMENT ...
Page 380: ...9 SYSTEM UTILITIES ...
Page 424: ...10 COMPONENT DESCRIPTIONS ...
Page 465: ...11 OPTIONAL FEATURES ...
Page 485: ...12 RELEASE 1 55 UPGRADE INSTRUCTIONS ...
Page 516: ...13 RELEASE 2 X UPGRADE INSTRUCTIONS ...
Page 559: ...14 RELEASE 3 02 FCP CONVERSION INSTRUCTIONS ...
Page 603: ...15 RELEASE 3 02 ONLINE UPGRADE INSTRUCTIONS ...
Page 631: ...16 RELEASE 3 0 SYSTEM UTILITIES ...
Page 683: ...17 RELEASE 4 X FCP CONVERSION INSTRUCTIONS r P N 281 0023 002 1 of 3 ...
Page 725: ...18 RELEASE 4 X ONLINE UPGRADE INSTRUCTIONS r P N 281 0023 002 2 of 3 ...
Page 760: ...19 RELEASE 4 0 SYSTEM UTILITIES P N 281 0023 002 Part 3 of 3 r ...
Page 776: ...20 RELEASE 4 1 SYSTEM UTILITIES P N 281 0033 000 ...
Page 787: ...APPENDIXES ...