The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the APPxVAL output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the APPxVAL output will be LOW.
17.4.12
GOOSE binary receive GOOSEBINRCV
SEMOD173158-1 v3
17.4.12.1
Function block
SEMOD173175-4 v2
IEC07000047-4-en.vsd
GOOSEBINRCV
BLOCK
^SRCOUT1
^SRCOUT2
^SRCOUT3
^SRCOUT4
^SRCOUT5
^SRCOUT6
^SRCOUT7
^SRCOUT8
^SRCOUT9
^SRCOUT10
^SRCOUT11
^SRCOUT12
^SRCOUT13
^SRCOUT14
^SRCOUT15
^SRCOUT16
^OUT1
DVALID1
^OUT2
DVALID2
^OUT3
DVALID3
^OUT4
DVALID4
^OUT5
DVALID5
^OUT6
DVALID6
^OUT7
DVALID7
^OUT8
DVALID8
^OUT9
DVALID9
^OUT10
DVALID10
^OUT11
DVALID11
^OUT12
DVALID12
^OUT13
DVALID13
^OUT14
DVALID14
^OUT15
DVALID15
^OUT16
DVALID16
COMMVALID
TEST
IEC07000047 V4 EN-US
Figure 349:
GOOSEBINRCV function block
17.4.12.2
Signals
SEMOD173166-1 v2
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These
connections are visible and possible to make only if Easy GOOSE
engineering is enabled. For instructions on how to enable Easy
GOOSE engineering in PCM600, refer to the
Engineering Manual
.
Section 17
1MRK 506 382-UEN A
Station communication
692
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...