14.9.6
Monitored data
PID-3906-MONITOREDDATA v1
Table 441:
LMBRFLO Monitored data
Name
Type
Values (Range)
Unit
Description
FLT_REL
REAL
-
-
Distance to fault, relative
FLT_DIST
REAL
-
-
Distance to fault in line
length unit
FLT_X
REAL
-
Ohm
Reactive distance to
fault
FLT_R
REAL
-
Ohm
Resistive distance to
fault
FLT_LOOP
INTEGER
1=L1-N
2=L2-N
3=L3-N
4=L1-L2
5=L2-L3
6=L3-L1
7=Others
-
Fault loop
14.9.7
Operation principle
M14982-4 v7
The Fault locator (LMBRFLO) in the IED is an essential complement to other
monitoring functions, since it measures and indicates the distance to the fault with
high accuracy.
When calculating distance to fault, pre-fault and fault phasors of currents and
voltages are selected from the Trip value recorder data, thus the analog signals used
by the fault locator must be among those connected to the disturbance report
function. The analog configuration (channel selection) is performed using the
parameter setting tool within PCM600.
The calculation algorithm considers the effect of load currents, double-end infeed
and additional fault resistance.
Z
0m
=Z
0m
+jX
0m
R
1A
+jX
1A
R
0L
+jX
0L
R
1L
+jX
1L
R
0L
+jX
0L
R
1L
+jX
1L
R
1B
+jX
1B
IEC05000045_2_en.vsd
LMBRFLO
DRPRDRE
IEC05000045 V2 EN-US
Figure 317:
Simplified network configuration with network data, required for
settings of the fault location-measuring function
1MRK 506 382-UEN A
Section 14
Monitoring
Line distance protection REL650 2.2 IEC
625
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...