(*)Set value for t: XDbRepInt
t (*)
t (*)
t (*)
t (*)
IEC05000500 V2 EN-US
Figure 283:
Periodic reporting
Amplitude dead-band supervision
SEMOD54417-163 v6
If a measuring value is changed, compared to the last reported value, and the
change is larger than the ±ΔY pre-defined limits that are set by user (
XDbRepInt
),
then the measuring channel reports the new value to a higher level. This limits the
information flow to a minimum necessary. Figure
amplitude dead-band supervision. The picture is simplified: the process is not
continuous but the values are evaluated with a time interval of one execution cycle
from each other.
1MRK 506 382-UEN A
Section 14
Monitoring
Line distance protection REL650 2.2 IEC
553
Technical manual