12.2.7
Technical data
M16039-1 v16
Table 259:
ZCRWPSCH technical data
Function
Range or value
Accuracy
Detection level phase-to-neutral
voltage
(10-90)% of UBase
±0.5% of U
r
Detection level phase-to-phase
voltage
(10-90)% of UBase
±0.5% of U
r
Operate time for current reversal
logic
(0.000-60.000) s
±0.2% or ±15 ms
whichever is greater
Delay time for current reversal
(0.000-60.000) s
±0.2% or ±15 ms
whichever is greater
Coordination time for weak-end
infeed logic
(0.000-60.000) s
±0.2% or ±15 ms
whichever is greater
12.3
Local acceleration logic ZCLCPSCH
SEMOD52894-1 v4
12.3.1
Identification
M14860-1 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local acceleration logic
ZCLCPSCH
-
-
12.3.2
Functionality
M13823-3 v7
To achieve fast clearing of faults on the whole line, when no communication
channel is available, local acceleration logic (ZCLCPSCH) can be used. This logic
enables fast fault clearing and re-closing during certain conditions, but naturally, it
can not fully replace a communication channel.
The logic can be controlled either by the autorecloser (zone extension) or by the
loss-of-load current (loss-of-load acceleration).
12.3.3
Function block
M13816-3 v4
ZCLCPSCH
I3P*
BLOCK
ARREADY
NDST
EXACC
BC
LLACC
TRZE
TRLL
IEC13000307-1-en.vsd
IEC13000307 V1 EN-US
Figure 228:
ZCLCPSCH function block
Section 12
1MRK 506 382-UEN A
Scheme communication
446
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...