Name
Values (Range)
Unit
Step
Default
Description
tIReset2
0.000 - 60.000
s
0.001
0.025
Time delay in IDMT reset (s), step 2
ACrv2
0.005 - 200.000
-
0.001
1.000
Parameter A for customer programmable
curve for step 2
BCrv2
0.50 - 100.00
-
0.01
1.00
Parameter B for customer programmable
curve for step 2
CCrv2
0.0 - 1.0
-
0.1
0.0
Parameter C for customer
programmable curve for step 2
DCrv2
0.000 - 60.000
-
0.001
0.000
Parameter D for customer
programmable curve for step 2
PCrv2
0.000 - 3.000
-
0.001
1.000
Parameter P for customer programmable
curve for step 2
CrvSat2
0 - 100
%
1
0
Tuning param for prog. under voltage
IDMT curve, step 2
Table 144:
UV2PTUV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ConnType
PhN DFT
PhPh RMS
PhN RMS
PhPh DFT
-
-
PhN DFT
Group selector for connection type
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
8.1.6
Monitored data
PID-3586-MONITOREDDATA v6
Table 145:
UV2PTUV Monitored data
Name
Type
Values (Range)
Unit
Description
UL1
REAL
-
kV
Voltage in phase L1
UL2
REAL
-
kV
Voltage in phase L2
UL3
REAL
-
kV
Voltage in phase L3
8.1.7
Operation principle
M15326-3 v9
Two-step undervoltage protection (UV2PTUV) is used to detect low power system
voltage. If one, two or three phase voltages decrease below the set value, a
corresponding START signal is generated. The parameters
OpMode1
and
OpMode2
influence the requirements to activate the START outputs: the measured
voltages
1 out of 3
,
2 out of 3
, or
3 out of 3
have to be lower than the corresponding
set point to issue the corresponding START signal.
UV2PTUV has two voltage-measuring steps with separate time delays. If the
voltage remains below the set value for the chosen time delay, the corresponding
trip signal is issued. To avoid an unwanted trip due to the disconnection of the
related high-voltage equipment, a voltage-controlled blocking of the function is
1MRK 506 382-UEN A
Section 8
Voltage protection
Line distance protection REL650 2.2 IEC
263
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...