10.2.8
Technical data
M16069-1 v12
Table 187:
FUFSPVCtechnical data
Function
Range or value
Accuracy
Operate voltage, zero sequence
(1-100)% of UBase
±0.5% of U
r
Operate current, zero sequence
(1–100)% of IBase
±0.5% of I
r
Operate voltage, negative sequence
(1-100)% of UBase
±0.5% of U
r
Operate current, negative sequence
(1–100)% of IBase
±0.5% of I
r
Operate voltage change level
(1-100)% of UBase
±10.0% of U
r
Operate current change level
(1–100)% of IBase
±10.0% of I
r
Operate phase voltage
(1-100)% of UBase
±0.5% of U
r
Operate phase current
(1–100)% of IBase
±0.5% of I
r
Operate phase dead line voltage
(1-100)% of UBase
±0.5% of U
r
Operate phase dead line current
(1–100)% of IBase
±0.5% of I
r
Operate time, start, 1 ph, at 1 x U
r
to 0
Min. = 10 ms
Max. = 25 ms
-
Reset time, start, 1 ph, at 0 to 1 x U
r
Min. = 15 ms
Max. = 30 ms
-
1MRK 506 382-UEN A
Section 10
Secondary system supervision
Line distance protection REL650 2.2 IEC
331
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...