Frequency
f < StartFrequency
Voltage
start
TRIP
RESTORE
U < IntBlockLevel
block
f > RestoreFreq
BLOCK
OR
Definite timer
or
Voltage based timer
tReset
tDelay
tRestore
restore
IEC16000041-1-en.vsdx
trip
START
BLKTRIP
AND
Start
&
Trip
output
logic
BLKREST
AND
BLKDMAGN
IEC16000041 V1 EN-US
Figure 152:
Simplified logic diagram for SAPTUF
9.1.7
Technical data
M13360-1 v15
Table 165:
SAPTUF technical data
Function
Range or value
Accuracy
Operate value, start function, at symmetrical three
phase voltage
(35.00-75.00) Hz
±2.0 mHz
Operate time, start at f
set
+ 0.02 Hz to f
set
- 0.02 Hz
fn = 50 Hz
Min. = 80 ms
-
Max. = 95 ms
fn = 60 Hz
Min. = 65 ms
Max. = 80 ms
Reset time, start at f
set
- 0.02 Hz to f
set
+ 0.02 Hz
Min. = 15 ms
Max. = 30 ms
-
Operate time, definite time function at f
set
+ 0.02 Hz
to f
set
- 0.02 Hz
(0.000-60.000)s
±0.2% or
±100 ms
whichever
is greater
Table continues on next page
Section 9
1MRK 506 382-UEN A
Frequency protection
304
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...