where:
Un>
Set value for step 1 and step 2
U
Measured voltage
The type B curve is described as:
2.0
480
0.035
32
0.5
n
n
k
t
U
U
U
IECEQUATION2423 V2 EN-US
(Equation 45)
The type C curve is described as:
3.0
480
0.035
32
0.5
n
n
k
t
U U
U
×
=
+
æ
ö
-
>
×
-
ç
÷
>
è
ø
IECEQUATION2425 V1 EN-US
(Equation 46)
The customer programmable curve is defined by the below equation, where A, B,
C, D, k and p are settings:
p
n
n
k A
t
D
U U
B
C
U
×
=
+
æ
ö
-
>
×
-
ç
÷
>
è
ø
EQUATION1439 V2 EN-US
(Equation 47)
When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore, a tuning parameter
CrvSatn
is set to compensate for this phenomenon. In the voltage interval Un> up
to Un> · (1.0 +
CrvSatn
/100) the used voltage will be: Un> · (1.0 +
CrvSatn
/100).
If the programmable curve is used this parameter must be calculated so that:
0
100
CrvSatn
B
C
×
- >
EQUATION1435 V1 EN-US
(Equation 48)
The highest phase (or phase-to-phase) voltage is always used for the inverse time
delay integration, see figure
. The details of the different inverse time
characteristics are shown in section
1MRK 506 382-UEN A
Section 8
Voltage protection
Line distance protection REL650 2.2 IEC
279
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...