A time extension delay,
tExtended t1
, can be added to the dead time delay for the
first shot. It is intended to come into use if the communication channel for
permissive line protection is lost. In a case like this there can be a significant time
difference in fault clearance at the two line ends, where a longer auto reclosing
dead time can be useful. This time extension is controlled by the setting
Extended
t1
and the
PLCLOST
input. The logic for control of extended dead time is shown in
. Time extension delay is not possible to add to the three-
phase high-speed auto reclosing dead time,
t1 3PhHS
.
Extended t1
AND
OR
PLCLOST
initiate
AND
start
AND
extendTime
IEC16000155-1-en.vsdx
IEC16000155 V1 EN-US
Figure 177:
Control of extended dead time
Shots 2 to 5 are all three-phase shots and have only one corresponding time setting
each,
t2 3Ph
,
t3 3Ph
,
t4 3Ph
and
t5 3Ph
.
Starting auto reclosing
GUID-7794EA6E-7D73-46BD-A623-65DED8E45D05 v1
When a start is applied to the auto function, it status will change from “ready”
status to “in progress” status. When the dead time has expired, the close command
is issued and the reclaim time is started and the “in progress” status will change to
“reclaim time” status.
The usual way to start a reclosing sequence, is to start it when a selective line
protection tripping has occurred, by applying a signal to the
START
input. If the
auto reclosing mode with only three-phase reclosing is selected, activation of the
START
input will start the three-phase dead timer. When alternatively the
START
input signal is applied, and an auto reclosing mode with single-phase reclosing is
selected, the auto reclosing dead time for single-phase is used. However if one of
the
TR2P
or
TR3P
inputs is activated in connection with the
START
input, the auto
reclosing dead time for two-phase or three-phase auto reclosing is used. The
STARTHS
input (start high-speed reclosing) can also be used to start a separate,
high-speed three-phase dead time in which case the synchrocheck condition will be
bypassed.
To start a new auto reclosing cycle, a number of conditions of input signals need to
be fulfilled. The inputs are:
Section 11
1MRK 506 382-UEN A
Control
364
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...