The CT and VT ratio and the name on respective channel is done under
IED
Configuration/HW Configuration/ADM
in the Parameter Settings Tool or under
Main menu/Configuration/Analog modules
in the HMI.
3.7
Technical data
SEMOD55412-1 v1
M16988-1 v11
Table 17:
TRM - Energizing quantities, rated values and limits for protection transformer
Description
Value
Frequency
Rated frequency f
r
50/60 Hz
Operating range
f
r
± 10%
Current inputs
Rated current I
r
1 or 5 A
Operating range
(0-100) x I
r
Thermal withstand
100 × I
r
for 1 s *)
30 × I
r
for 10 s
10 × I
r
for 1 min
4 × I
r
continuously
Dynamic withstand
250 × I
r
one half wave
Burden
< 20 mVA at I
r
= 1 A
< 150 mVA at I
r
= 5 A
*) max. 350 A for 1 s when COMBITEST test switch is included.
Voltage inputs **)
Rated voltage U
r
110 or 220 V
Operating range
0 - 340 V
Thermal withstand
450 V for 10 s
420 V continuously
Burden
< 20 mVA at 110 V
< 80 mVA at 220 V
**) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency
SEMOD53376-2 v6
Table 18:
CT and VT circuit connectors
Connector type
Rated voltage and current
Maximum conductor area
Screw compression type
250 V AC, 20 A
4 mm
2
(AWG12)
2 x 2.5 mm
2
(2 x AWG14)
Terminal blocks suitable for
ring lug terminals
250 V AC, 20 A
4 mm
2
(AWG12)
Section 3
1MRK 506 382-UEN A
Analog inputs
60
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...