17.8.15.3
Function block
GUID-031C0F49-BEBD-40FE-A33F-18F1D94BB4B0 v1
I103POSCMDV
BLOCK
POSITION
IEC15000081-2-en.vsdx
IEC15000081 V2 EN-US
Figure 374:
I103POSCMDV function block
17.8.15.4
Signals
PID-6578-INPUTSIGNALS v5
Table 555:
I103POSCMDV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
POSITION
INTEGER
0
Position of controllable object
17.8.15.5
Settings
PID-6578-SETTINGS v6
Table 556:
I103POSCMDV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type
InfNo
160 - 209
-
1
160
Information number for command output
17.8.16
Operation principle
IP14407-1 v3
17.8.16.1
General
M11874-3 v5
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system, and with a data
transfer rate up to 38400 bit/s. In IEC terminology, a primary station is a master
and a secondary station is a slave. The communication is based on a point-to-point
principle. The master must have software that can interpret IEC 60870-5-103
communication messages.
Introduction to IEC 60870–5–103 protocol
M11874-6 v3
IEC 60870-5-103 protocol functionality consists of the following functions:
•
Event handling
•
Report of analog service values (measurements)
•
Fault location
•
Command handling
Section 17
1MRK 506 382-UEN A
Station communication
760
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...