IEC99000529-2-en.vsdx
Y
t
Value Reported
(1st)
Value Reported
Value Reported
Y1
Y2
Y3
Y
Y
Y
Y
Y
Y
Value Reported
IEC99000529 V2 EN-US
Figure 51:
Amplitude dead-band supervision reporting
After the new value is reported, the ±ΔY limits for dead-band are automatically set
around it. The new value is reported only if the measured quantity changes more
than defined by the ±ΔY set limits.
Integral dead-band reporting
SEMOD54417-167 v4
The measured value is reported if the time integral of all changes exceeds the pre-
set limit (
XDbRepInt
, where an example of reporting with integral dead-
band supervision is shown. The picture is simplified: the process is not continuous
but the values are evaluated with a time interval of one execution cycle from each
other.
The last value reported, Y1 in figure
serves as a basic value for further
measurement. A difference is calculated between the last reported and the newly
measured value and is multiplied by the time increment (discrete integral). The
absolute values of these integral values are added until the pre-set value is
exceeded. This occurs with the value Y2 that is reported and set as a new base for
the following measurements (as well as for the values Y3, Y4 and Y5).
The integral dead-band supervision is particularly suitable for monitoring signals
with small variations that can last for relatively long periods.
1MRK 506 382-UEN A
Section 6
Impedance protection
Line distance protection REL650 2.2 IEC
119
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...