![ABB RELION 650 SERIES Technical Manual Download Page 65](http://html.mh-extra.com/html/abb/relion-650-series/relion-650-series_technical-manual_2122065.webp)
3.6
Operation principle
SEMOD55028-5 v9
The direction of a measured current depends on the connection of the CT. The main
CTs are typically star connected and can be connected with the star point towards
the object or away from the object. This information must be set in the IED.
Once the CT direction settings is correctly entered the internal IED convention of
the directionality is defined as follows:
•
Positive value of current or power means that the quantity has the direction
into the protected object.
•
Negative value of current or power means that the quantity has the direction
out from the protected object.
For directional functions the directional conventions are defined as follows (see
Figure
•
Forward
means the direction is into the object.
•
Reverse
means the direction is out from the object.
Protected Object
Line, transformer, etc
Forward
Reverse
Definition of direction
for directional functions
Measured quantity is
positive when flowing
towards the object
e.g. P, Q, I
Reverse
Forward
Definition of direction
for directional functions
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CTStarPoint
Correct Setting is
"ToObject"
Set parameter
CTStarPoint
Correct Setting is
"FromObject"
en05000456.vsd
IEC05000456 V1 EN-US
Figure 2:
Internal convention of the directionality in the IED
If the settings of the primary CT is correct, that is
CTStarPoint
set as
FromObject
or
ToObject
according to the plant condition, then a positive quantity always flows
towards the protected object, and a
Forward
direction always looks towards the
protected object.
The settings of the IED is performed in primary values. The ratios of the main CTs
and VTs are, therefore, basic data for the IED. The user has to set the rated
secondary and primary currents and voltages of the CTs and VTs to provide the
IED with their rated ratios.
1MRK 506 382-UEN A
Section 3
Analog inputs
Line distance protection REL650 2.2 IEC
59
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...