11.5.5
Settings
PID-6641-SETTINGS v3
Table 232:
SLGAPC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
NrPos
2 - 32
-
1
32
Number of positions in the switch
OutType
Pulsed
Steady
-
-
Steady
Output type, steady or pulse
tPulse
0.000 - 60.000
s
0.001
0.200
Operate pulse duration, in [s]
tDelay
0.000 - 60000.000
s
0.010
0.000
Time delay on the output, in [s]
StopAtExtremes
Disabled
Enabled
-
-
Disabled
Stop when min or max position is
reached
11.5.6
Monitored data
PID-6641-MONITOREDDATA v3
Table 233:
SLGAPC Monitored data
Name
Type
Values (Range)
Unit
Description
SWPOSN
INTEGER
-
-
Switch position (integer)
11.5.7
Operation principle
SEMOD114931-4 v7
The logic rotating switch for function selection and LHMI presentation (SLGAPC)
function has two operating inputs – UP and DOWN. When a signal is received on
the UP input, the function will activate the output next to the present activated
output, in ascending order (for example if the present activated output is P03 and
one activates the UP input then the output P04 will be activated). When a signal is
received on the DOWN input, the function will activate the output next to the
present activated output, in descending order (for example if the present activated
output is P03 and one activates the DOWN input then the output P02 will be
activated). Depending on the output settings the output signals can be steady or
pulsed. In case of steady signals, the output will be active till the time it receives
next operation of UP/DOWN inputs. Also, depending on the settings one can have
a time delay between activation of the UP or DOWN input signals and the output
activation.
Besides the inputs visible in the application configuration in the Application
Configuration Tool, there are other possibilities that will allow an user to set the
desired position directly (without activating the intermediate positions), either
locally or remotely, using a “select before execute” dialog. One can block the
function operation, by activating the BLOCK input. In this case, the present
position will be kept and further operation will be blocked. The operator place
(local or remote) is specified through the PSTO input. If any operation is allowed
the signal INTONE from the Fixed signal function block can be connected.
1MRK 506 382-UEN A
Section 11
Control
Line distance protection REL650 2.2 IEC
417
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...