Information number is defined for each output signals.
Table 558:
Pre-defined I103CMD supported indications
INF
Description
16
Auto-recloser on/off
17
Teleprotection on/off
18
Protection on/off
Function commands in control direction, user-defined, I103USRCMD
M11874-72 v6
Function command blocks in control direction with user-defined output signals.
Number of instances: 4
Function type for each function block instance in private range is selected with
parameter
FunctionType
.
Information number must be selected for each output signal. Default values are 1 -
8.
Table 559:
I103USRCMD supported indications
INF
1)
Description
1
Output signal 01
2
Output signal 02
3
Output signal 03
4
Output signal 04
5
Output signal 05
6
Output signal 06
7
Output signal 07
8
Output signal 08
1) User defined information number
Status
M11874-107 v1
Terminal status indications in monitor direction, I103IED
M11874-109 v7
Indication block for status in monitor direction with defined IED functions.
Number of instances: 1
Function type is selected with parameter
FunctionType
.
Information number is defined for each input signals.
Section 17
1MRK 506 382-UEN A
Station communication
762
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...