20.2.8.2
Design
M1819-3 v4
The binary output module (BOM) has 24 software supervised output relays. Each
pair of relays have a common power source input to the contacts, see figure
This should be considered when connecting the wiring to the connection terminal
on the back of the IED.
The high closing and carrying current capability allows connection directly to
breaker trip and closing coils. If breaking capability is required to manage fail of
the breaker auxiliary contacts normally breaking the trip coil current, a parallel
reinforcement is required.
For configuration of the output signals, refer to section
xx00000299.vsd
2
1
3
Output module
IEC00000299 V1 EN-US
Figure 403:
Relay pair example
1 Output connection from relay 1
2 Output signal power source connection
3 Output connection from relay 2
1MRK 506 382-UEN A
Section 20
IED hardware
Line distance protection REL650 2.2 IEC
847
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...