17.4.11.3
Signals
SEMOD173205-1 v2
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These
connections are visible and possible to make only if Easy GOOSE
engineering is enabled. For instructions on how to enable Easy
GOOSE engineering in PCM600, refer to the
Engineering Manual
.
PID-6831-INPUTSIGNALS v3
Table 501:
GOOSEINTLKRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of output signals
SRCRESREQ
BOOLEAN
0
Source to reservation request
SRCRESGR
BOOLEAN
0
Source to reservation granted
SRCAPP1
INTEGER
0
Source to apparatus 1 position
SRCAPP2
INTEGER
0
Source to apparatus 2 position
SRCAPP3
INTEGER
0
Source to apparatus 3 position
SRCAPP4
INTEGER
0
Source to apparatus 4 position
SRCAPP5
INTEGER
0
Source to apparatus 5 position
SRCAPP6
INTEGER
0
Source to apparatus 6 position
SRCAPP7
INTEGER
0
Source to apparatus 7 position
SRCAPP8
INTEGER
0
Source to apparatus 8 position
SRCAPP9
INTEGER
0
Source to apparatus 9 position
SRCAPP10
INTEGER
0
Source to apparatus 10 position
SRCAPP11
INTEGER
0
Source to apparatus 11 position
SRCAPP12
INTEGER
0
Source to apparatus 12 position
SRCAPP13
INTEGER
0
Source to apparatus 13 position
SRCAPP14
INTEGER
0
Source to apparatus 14 position
SRCAPP15
INTEGER
0
Source to apparatus 15 position
PID-6831-OUTPUTSIGNALS v3
Table 502:
GOOSEINTLKRCV Output signals
Name
Type
Description
RESREQ
BOOLEAN
Reservation request
RESGRANT
BOOLEAN
Reservation granted
APP1_OP
BOOLEAN
Apparatus 1 position is open
APP1_CL
BOOLEAN
Apparatus 1 position is closed
APP1VAL
BOOLEAN
Apparatus 1 position is valid
APP2_OP
BOOLEAN
Apparatus 2 position is open
APP2_CL
BOOLEAN
Apparatus 2 position is closed
APP2VAL
BOOLEAN
Apparatus 2 position is valid
Table continues on next page
1MRK 506 382-UEN A
Section 17
Station communication
Line distance protection REL650 2.2 IEC
689
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...