This variant has the possibility of choice between definite time delay and inverse
time delay.
The inverse time delay is defined as:
0
0
inv
0
0
kSN (3I 3U cos (reference))
t
3I 3U cos (measured)
×
×
×
j
=
×
×
j
EQUATION1942 V2 EN-US
(Equation 30)
Directional residual current protection measuring 3I
0
and φ
SEMOD171963-48 v4
The function will operate if the residual current is larger than the set value and the
angle |φ = ang(3I
0
)-ang(U
ref
)| is within the sector
RCADir
±
ROADir
-3U
0
Operate area
3I
0
RCADir
= 0º
ROADir
= 80º
IEC06000652-3-en.vsd
IEC06000652 V3 EN-US
Figure 108:
Example of characteristic
For trip, Residual current 3I
0
shall be larger than both
INRel>
and
INDir>
, and
residual voltage 3U
0
shall be larger than the
UNRel>
. In addition, the angle φ shall
be in the set area defined by
ROADir
and
RCADir
. Refer to the simplified logical
diagram in Figure
.
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function picks up, binary output signals START and STDIRIN are
activated. If the output signals START and STDIRIN remain active for the set
delay
tDef
the binary output signals TRIP and TRDIRIN get activated.
The function indicates forward/reverse direction to the fault. Reverse direction is
defined as φ is within the angle sector:
RCADir
+ 180° ±
ROADir
This variant has definite time delay.
1MRK 506 382-UEN A
Section 7
Current protection
Line distance protection REL650 2.2 IEC
227
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...