execute command
SY_INPRO
SYNC_OK
t2>tSynchronizing, then
blocked-by-synchrocheck in
'cause' is set
tSynchrocheck
t1
START_SY
tSynchronizing
t2
en05000095.vsd
IEC05000095 V1 EN-US
Figure 201:
tSynchroCheck and tSynchronizing
11.4.6.6
Interaction with switch on process bus
GUID-1E243260-55FC-4DA6-A314-649E0B95A2B9 v1
When the switches are modelled and controlled in a breaker IED, the information
from the switches is limited to those described in the IEC 61850 standard.
Since there is no expression for distributing the cause of failure over GOOSE, the
XLNPROXY function is used for evaluating the causes normally evaluated by the
SXCBR function.
Further, in some cases selection may also be used on the model of the switch in the
breaker IED, in case multiple controllers may access it via GOOSE. In such a case,
if the input for the
stSeld
data attribute in the XLNPROXY function is connected,
SCSWI automatically awaits that the switch is selected before accepting the
selection. Also, if the
seSeld
data attribute is set before the selection is requested,
the selection request fails.
Section 11
1MRK 506 382-UEN A
Control
402
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...