contacts have the same value or if the auxiliary input contact
POSCLOSE
is low
and the
POSOPEN
input is high but the current is above the setting
AccStopCurr
.
The status of the breaker is indicated with the binary outputs
OPENPOS
,
CLOSEPOS
and
INVDPOS
for open, closed and error position respectively.
14.4.7.3
Remaining life of circuit breaker
GUID-C347406A-2B6F-42BD-B70B-51489AB51EAE v12
The Remaining life of circuit breaker subfunction is used to give an indication on
the wear and tear of the circuit breaker. Every time the breaker operates, the life of
the circuit breaker reduces due to wear. The breaker wear depends on the
interrupted current. The remaining life of the breaker is estimated from the circuit
breaker trip curve provided by the manufacturer. The remaining life is decreased by
at least one when the circuit breaker is opened. The operation of the remaining life
of circuit breaker subfunction is described in figure
POSCLOSE
BLOCK
BLKALM
CB remaining
life estimation
Alarm limit
Check
I3P-ILRMSPH
RSTCBWR
CBLIFEPH
CBLIFEAL
IEC12000620-3-en.vsd
IEC12000620 V3 EN-US
Figure 296:
Functional module diagram for estimating the life of the circuit
breaker
Circuit breaker remaining life estimation
If the interrupted current is less than the rated operating current set using the
RatedOperCurr
setting, the remaining operations of the breaker are reduced by one
operation. If the interrupted current is more than the rated fault current set using the
RatedFltCurr
setting, the remaining operations of the circuit breaker are reduced
by the set
OperNoRated
divided by the set
OperNoFault
value. If the tripping
current is between these two values, the remaining life of the circuit breaker is
calculated based on the maintenance curve equation given by the manufacturer.
The
OperNoRated
parameter sets the number of operations the breaker can perform
at the rated current. The
OperNoFault
parameter sets the number of operations the
breaker can perform at the rated fault current.
Alarm limit check
When the remaining life of a circuit breaker phase drops below the
CBLifeAlmLevel
setting, the life alarm
CBLIFEAL
is activated.
It is possible to deactivate the
CBLIFEAL
alarm signal by activating the binary
input
BLKALM
.
1MRK 506 382-UEN A
Section 14
Monitoring
Line distance protection REL650 2.2 IEC
579
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...