Section 10
Secondary system supervision
10.1
Current circuit supervision CCSSPVC
IP14555-1 v5
10.1.1
Identification
M14870-1 v5
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current circuit supervision
CCSSPVC
-
87
10.1.2
Functionality
M12444-3 v10
Open or short circuited current transformer cores can cause unwanted operation of
many protection functions such as differential, earth-fault current and negative-
sequence current functions.
Current circuit supervision (CCSSPVC) compares the residual current from a three
phase set of current transformer cores with the neutral point current on a separate
input taken from another set of cores on the current transformer.
A detection of a difference indicates a fault in the circuit and is used as alarm or to
block protection functions expected to give inadvertent tripping.
10.1.3
Function block
M12436-3 v9
CCSSPVC
I3P*
IREF*
BLOCK
FAIL
ALARM
IEC13000304-1-en.vsd
IEC13000304 V1 EN-US
Figure 157:
CCSSPVC function block
Signal ISIREF must be connected in the configuration.
1MRK 506 382-UEN A
Section 10
Secondary system supervision
Line distance protection REL650 2.2 IEC
315
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...