Function
Range or value
Accuracy
Time delay for temperature
alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Reset time delay for
temperature alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Time delay for temperature
lockout
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
14.3
Liquid medium supervision SSIML
GUID-37669E94-4830-4C96-8A67-09600F847F23 v3
14.3.1
Identification
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation liquid monitoring function
SSIML
-
71
14.3.2
Functionality
GUID-3B1A665F-60A5-4343-85F4-AD9C066CBE8D v6
Insulation supervision for liquid medium (SSIML) is used for monitoring the
transformer condition. Binary information based on the oil level in the transformer
is used as input signals to the function. In addition, the function generates alarms
based on received information.
14.3.3
Function block
GUID-AC82A86C-495D-4CBD-9BF9-3CC760591AA9 v3
SSIML
BLOCK
BLKALM
SENLEVEL
SENTEMP
SENLVLALM
SENLVLLO
SETLLO
SETTLO
RESETLO
LOCKOUT
LVLLO
TEMPLO
ALARM
LVLALM
TEMPALM
LEVEL
TEMP
IEC09000128-2-en.vsdx
IEC09000128 V2 EN-US
Figure 290:
SSIML function block
14.3.4
Signals
GUID-0C378BB3-2104-417F-94B5-16EFC55151FE v2
Section 14
1MRK 506 382-UEN A
Monitoring
568
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...