6.4.3
Function block
GUID-CB98C615-8A93-438D-9DF0-542F333198AC v4
OOSPPAM
I3P1*
I3P2*
U3P*
BLOCK
BLKGEN
BLKMOT
EXTZ1
TRIP
TRIPZ1
TRIPZ2
START
GENMODE
MOTMODE
R
X
SLIPFREQ
ROTORANG
UCOSPHI
IEC12000188-3-en.vsd
IEC12000188 V3 EN-US
Figure 60:
OOSPPAM function block
6.4.4
Signals
PID-3539-INPUTSIGNALS v10
Table 50:
OOSPPAM Input signals
Name
Type
Default
Description
I3P1
GROUP
SIGNAL
-
Group connection for three-phase current input 1
I3P2
GROUP
SIGNAL
-
Group connection for three-phase current input 2
U3P
GROUP
SIGNAL
-
Group connection for three-phase voltage input
BLOCK
BOOLEAN
0
Block of function
BLKGEN
BOOLEAN
0
Block operation in generating direction
BLKMOT
BOOLEAN
0
Block operation in motor direction
EXTZ1
BOOLEAN
0
Extension of zone1 reach to zone2 settings
PID-3539-OUTPUTSIGNALS v10
Table 51:
OOSPPAM Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip, issued when either zone 1 or zone
2 give trip
TRIPZ1
BOOLEAN
Zone 1 trip
TRIPZ2
BOOLEAN
Zone 2 trip
START
BOOLEAN
Set when measured impedance enters lens
characteristic
GENMODE
BOOLEAN
Generator rotates faster than the system during
pole slip
MOTMODE
BOOLEAN
Generator rotates slower than the system during
pole slip
R
REAL
Real part of measured positive-sequence
impedance % of UBase/(sqrt(3)*IBase)
Table continues on next page
Section 6
1MRK 506 382-UEN A
Impedance protection
136
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...