6.5.5
Settings
PID-6809-SETTINGS v2
Table 60:
PPL2PHIZ Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
OperMode
No Filter
NoPref
1231c
1321c
123a
132a
213a
231a
312a
321a
-
-
No Filter
Operating mode (c=cyclic,a=acyclic)
UPN<
0 - 100
%UB/sq
3
1
70
Operate value of phase undervoltage in
% of UBase/sqrt(3)
UPP<
0 - 100
%UB
1
50
Operate value of line to line
undervoltage (% of UBase)
3U0>
5 - 300
%UB/sq
3
1
20
Operate value of residual voltage in % of
UBase/sqrt(3)
IN>
10 - 200
%IB
1
20
Operate value of residual current (% of
IBase)
tUN
0.000 - 60.000
s
0.001
0.100
Pickup-delay for residual voltage
tOffUN
0.000 - 60.000
s
0.001
0.100
Dropoff-delay for residual voltage
tIN
0.000 - 60.000
s
0.001
0.150
Pickup-delay for residual current
Table 61:
PPL2PHIZ Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
6.5.6
Operation principle
GUID-B304D0D3-1E4E-482D-975F-229467905608 v1
The PPL2PHIZ function releases the phase selection inside the distance protection,
see Figure
.
The phase selection inside the distance protection has to detect the
fault before an operation from the distance zones can be achieved,
even when the distance protection is released by PPL2PHIZ.
Section 6
1MRK 506 382-UEN A
Impedance protection
150
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...