The following table shows the relationship between IPOS1/IPOS2 inputs and the
name of the string that is shown on the SLD. The value of the strings are set in
PST.
IPOS1
IPOS2
Name of displayed
string
Default string value
0
0
PosUndefined
P00
1
0
Position1
P01
0
1
Position2
P10
1
1
PosBadState
P11
11.7
Generic communication function for Double Point
indication DPGAPC
SEMOD55384-1 v4
11.7.1
Identification
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Generic communication function for
Double Point indication
DPGAPC
-
-
11.7.2
Functionality
SEMOD55850-5 v7
Generic communication function for Double Point indication (DPGAPC) function
block is used to send double point position indications to other systems, equipment
or functions in the substation through IEC 61850-8-1 or other communication
protocols. It is especially intended to be used in the interlocking station-wide
logics.
11.7.3
Function block
SEMOD54710-4 v5
IEC13000081 V1 EN-US
Figure 212:
DPGAPC function block
Section 11
1MRK 506 382-UEN A
Control
422
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...