how to connect analog inputs, refer to
Application manual/IED application/
Analog inputs/Setting guidelines
.
9.2.3
Function block
M14956-3 v5
IEC06000280_2_en.vsd
SAPTOF
U3P*
BLOCK
BLKTRIP
TRIP
START
BLKDMAGN
FREQ
IEC06000280 V2 EN-US
Figure 153:
SAPTOF function block
9.2.4
Signals
PID-6751-INPUTSIGNALS v2
Table 166:
SAPTOF Input signals
Name
Type
Default
Description
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BLKTRIP
BOOLEAN
0
Blocking operate output
PID-6751-OUTPUTSIGNALS v2
Table 167:
SAPTOF Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
START
BOOLEAN
General start signal
BLKDMAGN
BOOLEAN
Blocking indication due to low amplitude
FREQ
REAL
Measured frequency
9.2.5
Settings
PID-6751-SETTINGS v2
Table 168:
SAPTOF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
StartFrequency
35.00 - 90.00
Hz
0.01
51.20
Frequency set value
IntBlockLevel
0.0 - 100.0
%UB
1.0
50.0
Internal blocking level in % of UBase
tDelay
0.000 - 60.000
s
0.001
0.000
Operate time delay
tReset
0.000 - 60.000
s
0.001
0.000
Time delay for reset
Section 9
1MRK 506 382-UEN A
Frequency protection
306
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...