5.3.3
Signals
PID-4114-INPUTSIGNALS v5
Table 23:
LEDGEN Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Input to block the operation of the LEDs
RESET
BOOLEAN
0
Input to acknowledge/reset the indication LEDs
PID-4114-OUTPUTSIGNALS v5
Table 24:
LEDGEN Output signals
Name
Type
Description
NEWIND
BOOLEAN
New indication signal if any LED indication input
is set
ACK
BOOLEAN
A pulse is provided when the LEDs are
acknowledged
PID-1697-INPUTSIGNALS v18
Table 25:
GRP1_LED1 Input signals
Name
Type
Default
Description
HM1L01R
BOOLEAN
0
Red indication of LED1, local HMI alarm group 1
HM1L01Y
BOOLEAN
0
Yellow indication of LED1, local HMI alarm group
1
HM1L01G
BOOLEAN
0
Green indication of LED1, local HMI alarm group
1
5.3.4
Settings
PID-4114-SETTINGS v6
Table 26:
LEDGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
tRestart
0.0 - 100.0
s
0.1
0.0
Defines the disturbance length
tMax
0.1 - 100.0
s
0.1
1.0
Maximum time for the definition of a
disturbance
1MRK 506 382-UEN A
Section 5
Local Human-Machine-Interface LHMI
Line distance protection REL650 2.2 IEC
65
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...