applicable to very long time accumulation (≤
99999.9
hours)
•
output
ACC_HOUR
presents accumulated value in hours and
ACC_DAY
presents accumulated value in days
•
accumulated value is retained in a non-volatile memory
•
any retained value is used as initiation value for the integration following
by a restart
•
RESET: Reset of the accumulated value. Consequently all other outputs are
also reset
•
independent of the input
IN
value
•
reset the value of the nonvolatile memory to zero.
Note that the nonvolatile memory will not reset to zero if the input
IN
is
high during the reset.
•
reset can be made by activation of input
RESET
or from LHMI or with
IEC 61850 command
•
ADDTIME: Manually add time to the currently accumulated time
•
the amount of time to be added is defined by a setting
tAddToTime
•
time is added through activation of input
ADDTIME
or from LHMI or
with IEC 61850 command
•
BLOCK: Freeze the accumulation and block/reset the other outputs
•
independent of the input
IN
value
•
BLOCK
request overrides
RESET
request
•
Monitor and report the conditions of limit transgression
•
overflow if output
ACC_HOUR
>
99 999.9
hours
•
alarm if output
ACC_HOUR
>
tAlarm
•
warning if output
ACC_HOUR
>
tWarning
The
ACC_HOUR
output represents the accumulated time in hours and the
ACC_DAY
output represents the accumulated time in days.
tAlarm
and
tWarning
are user settable time limit parameters in hours. They are also
independent of each other, that is, there is no check if
tAlarm
>
tWarning
.
tAddToTime
is a user settable time parameter in hours.
tAlarm
,
tWarning
and
tAddToTime
are possible to be defined with a resolution of
0.1 hours (6 minutes).
The limit for the overflow supervision is fixed at 99999.9 hours. The outputs will
reset and the accumulated time will reset and start from zero if an overflow occurs.
14.11.6.1
Operation accuracy
GUID-B6FBEFD7-17C8-41C6-B5D5-32E1205E6752 v1
The accuracy of TEILGAPC depends on essentially two factors
Section 14
1MRK 506 382-UEN A
Monitoring
638
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...