The logical value of the functional output signals changes according to figure
The user can set the hysteresis (
XLimHyst
), which determines the difference
between the operating and reset value at each operating point, in wide range for
each measuring channel separately. The hysteresis is common for all operating
values within one channel.
Actual value of the measured quantity
SEMOD54417-150 v4
The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting
of the value to the higher levels depends on the selected reporting mode. The
following basic reporting modes are available:
•
Cyclic reporting (
Cyclic
)
•
Amplitude dead-band supervision (
Dead band
)
•
Integral dead-band supervision (
Int deadband
)
•
Amplitude Deadband and 5s cyclic
•
Amplitude Deadband and 30s cyclic
•
Amplitude Deadband and 1min cyclic
Cyclic reporting
SEMOD54417-158 v3
The cyclic reporting of measured value is performed according to chosen setting
(
XRepTyp
). The measuring channel reports the value independent of amplitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.
Section 14
1MRK 506 382-UEN A
Monitoring
552
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...