14.7.5
Settings
PID-4144-SETTINGS v6
Table 433:
BINSTATREP Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
t
0.0 - 60.0
s
0.1
10.0
Time delay of function
14.7.6
Operation principle
GUID-537921CA-82B9-4A02-BAD1-67E3AC61AE96 v3
The Logical signal status report (BINSTATREP) function has 16 inputs and 16
outputs. The output status follows the inputs and can be read from the local HMI or
via SPA communication.
When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.
t
t
INPUTn
OUTPUTn
IEC09000732-1-en.vsd
IEC09000732 V1 EN-US
Figure 314:
BINSTATREP logical diagram
14.8
Measured value expander block RANGE_XP
SEMOD52451-1 v2
14.8.1
Identification
SEMOD113212-2 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block
RANGE_XP
-
-
14.8.2
Functionality
SEMOD52450-4 v7
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI
and VMSQI) and IEC 61850 generic communication I/O functions (MVGAPC) are
provided with measurement supervision functionality. All measured values can be
Section 14
1MRK 506 382-UEN A
Monitoring
620
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...