14.2.5
Settings
PID-6950-SETTINGS v6
Table 404:
SSIMG Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
PresAlmLimit
1.00 - 100.00
-
0.01
5.00
Alarm setting for pressure
PresLOLimit
1.00 - 100.00
-
0.01
3.00
Pressure lockout setting
TempAlarmLimit
-40.00 - 200.00
-
0.01
30.00
Temperature alarm level setting of the
medium
TempLOLimit
-40.00 - 200.00
-
0.01
30.00
Temperature lockout level of the medium
tPressureAlarm
0.000 - 60.000
s
0.001
0.000
Time delay for pressure alarm
tPressureLO
0.000 - 60.000
s
0.001
0.000
Time delay for pressure lockout
indication
tTempAlarm
0.000 - 60.000
s
0.001
0.000
Time delay for temperature alarm
tTempLockOut
0.000 - 60.000
s
0.001
0.000
Time delay for temperture lockout
tResetPresAlm
0.000 - 60.000
s
0.001
0.000
Reset time delay for pressure alarm
tResetPresLO
0.000 - 60.000
s
0.001
0.000
Reset time delay for pressure lockout
tResetTempLO
0.000 - 60.000
s
0.001
0.000
Reset time delay for temperture lockout
tResetTempAlm
0.000 - 60.000
s
0.001
0.000
Reset time delay for temperture alarm
14.2.6
Monitored data
PID-6950-MONITOREDDATA v5
Table 405:
SSIMG Monitored data
Name
Type
Values (Range)
Unit
Description
PRESSURE
REAL
-
-
Pressure service value
TEMP
REAL
-
deg
Temperature of the
insulation medium
14.2.7
Operation principle
GUID-359458EA-FFAA-4A44-A8E8-9469CA069C80 v7
Gas medium supervision SSIMG is used to monitor the gas pressure in the circuit
breaker. Binary inputs of gas density SENPRESALM, SENPRESLO, and gas
pressure signal SENPRES, are taken into account to initiate the alarm PRESALM
and the lockout PRESLO. When SENPRES is less than
PresAlmLimit
or binary
signal from CB SENPRESALM is high, the gas pressure alarm PRESALM will be
initiated. Similarly, if pressure input SENPRES is less than
PresLOLimit
or binary
signal from CB SENPRESLO is high, PRESLO will be initiated.
There may be sudden change in pressure of the gas for a very small time, for which
the function need not to initiate any alarm. To avoid the intermittent alarm, two
time delays
tPressureAlarm
or
tPressureLO
have been included. If the pressure
Section 14
1MRK 506 382-UEN A
Monitoring
566
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...