12.1.4
Signals
PID-3766-INPUTSIGNALS v7
Table 249:
ZCPSCH Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Current group connection
U3P
GROUP
SIGNAL
-
Voltage group connection
BLOCK
BOOLEAN
0
Block of function
BLKTR
BOOLEAN
0
Signal for block of trip output from communication
logic
BLKCS
BOOLEAN
0
Block of carrier send in permissive OR and
blocking schemes
CSBLK
BOOLEAN
0
Reverse directed distance protection zone signal
CACC
BOOLEAN
0
Permissive distance protection zone signal
CSOR
BOOLEAN
0
Overreaching distance protection zone signal
CSUR
BOOLEAN
0
Underreaching distance protection zone signal
CR
BOOLEAN
0
Carrier Signal Received
CRG
BOOLEAN
0
Carrier guard signal received
CBOPEN
BOOLEAN
0
Indicates that the breaker is open
PID-3766-OUTPUTSIGNALS v5
Table 250:
ZCPSCH Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip output
CS
BOOLEAN
Carrier Send signal
CHSTOP
BOOLEAN
Stops the blocking signal to remote end
CRL
BOOLEAN
Carrier signal received or missing carrier guard
signal
LCG
BOOLEAN
Loss of carrier guard signal
Section 12
1MRK 506 382-UEN A
Scheme communication
434
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...