SLGAPC function block has also an integer value output, that generates the actual
position number. The positions and the block names are fully settable by the user.
These names will appear in the menu, so the user can see the position names
instead of a number.
11.5.7.1
Graphical display
SEMOD114931-35 v4
There are two possibilities for SLGAPC
•
if it is used just for the monitoring, the switches will be listed with their actual
position names, as defined by the user (max. 13 characters).
•
if it is used for control, the switches will be listed with their actual positions,
but only the first three letters of the name will be used.
In both cases, the switch full name will be shown, but the user has to redefine it
when building the Graphical Display Editor, under the "Caption". If used for the
control, the following sequence of commands will ensure:
Section 11
1MRK 506 382-UEN A
Control
418
Line distance protection REL650 2.2 IEC
Technical manual