20.2.7.6
Technical data
SEMOD55338-1 v1
M12576-1 v9
Table 638:
BIM - Binary input module
Quantity
Rated value
Nominal range
Binary inputs
16
-
DC voltage, RL
24/30 V
48/60 V
110/125 V
220/250 V
RL
±
20%
RL
±
20%
RL
±
20%
RL
±
20%
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
-
Counter input frequency
10 pulses/s max
-
Oscillating signal discriminator
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Debounce filter
Settable 1–20 ms
M50609-2 v7
Table 639:
BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Rated value
Nominal range
Binary inputs
16
-
DC voltage, RL
24/30 V
48/60 V
110/125 V
220/250 V
RL
±
20%
RL
±
20%
RL
±
20%
RL
±
20%
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
-
Counter input frequency
10 pulses/s max
-
Balanced counter input frequency
40 pulses/s max
-
Oscillating signal discriminator
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Debounce filter
Settable 1-20 ms
20.2.8
Binary output modules (BOM)
IP14536-1 v1
20.2.8.1
Introduction
M6938-3 v4
The binary output module has 24 independent output relays and is used for trip
output or any signaling purpose.
Section 20
1MRK 506 382-UEN A
IED hardware
846
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...